GHBS & GBHS
Breaker Relay |
 Available
for |
|
|
|
 |
GHBS (UL Listed)
| Part
Numbers |
Number of Poles |
Interrupting Capacity (Symmetrical
Amperes) |
| Rating Amperes |
Volts AC (50/60
Hz) |
| 120 |
240 |
277/480 |
| GHBS1015D |
1 |
15 |
65,000 |
- |
14,000 |
| GHBS1020D |
1 |
20 |
65,000 |
- |
14,000 |
| GHBS1030D |
1 |
30 |
65,000 |
- |
14,000 |
| GHBS2015D |
2 |
15 |
- |
65,000 |
14,000 |
| GHBS2020D |
2 |
20 |
- |
65,000 |
14,000 |
| GHBS2030D |
2 |
30 |
- |
65,000 |
14,000 |
GBHS (CSA Approved)
| Part
Numbers |
Number of Poles |
Interrupting Capacity (Symmetrical
Amperes) |
| Rating Amperes |
Volts AC
(50/60 Hz) |
| 347/600 |
| GBHS1015D |
1 |
15 |
10,000 |
| GBHS1020D |
1 |
20 |
10,000 |
| GBHS2015D |
1 |
15 |
10,000 |
| GBHS2020D |
2 |
20 |
10 |
< Back to
top
|
|
|
 |
The Cutler Hammer Solenoid-Operated circuit breakers are
designed for use in panel board and are ideally suited for
retrofit lighting control applications. In replacement of
conventionnal branch circuit protection, they include a unique
solenoid-operated mechanism that provides for efficient breaker
pulse-on and pulse-off operation. These breakers can be mixed
with a group of standard breakers in the same breaker distribution
panel.
|
|
|
 |
|
Operating voltage:
|
24 V AC for an ½ cycle
|
| Three Position Handle: |
OFF, TRIP (center), ON |
|
In ON
= Position enables Remote Control
|
| In
OFF = Position disables Remote Control |
|
Handle
permits Manual Switching when Control Power is Lost
Mecanical
Trip Indicator Window (Red-On, Green-OFF/Tripped)
|
|
Electrical performance:
|
|
|
Fluorescent
lamp
|
20 A, 347 V AC
|
|
H.I.D.
Rated
|
20 A, 347 V AC
|
| I.C.
(Sym, 50/60 Hz) |
65 kA at 120, 240 Volts
14 kA at 277/480 Volts |
| Pole(s) |
1 or 2 poles |
| Auxiliary
switch for Control Circuit Feedback (Status) |
|
Test condition:
|
Switching cycle, 6 times/minute
|
|
Bi-Metal Assembly for Thermal Overlaod Protection
|
| Assembled: |
Distribution Panel series POWER-LINE
of Cutler Hammer, 1 or 3 phases, up to 480 volts, from
18 to 72 circuits; or in PDC in place of 3X cell |
|
Certification:
|

|
|
|
|